Title: Pastatų elektros instaliacijos ilgalaikio eksploatavimo įtakos gaisrų rizikai tyrimas
Other Title: Investigation of Long-Term Exploitation of Electric Installations on Fire Risk in Buildings
Extent: 45 p.
Date: 22-May-2013
Keywords: gaisras;rizika;instaliacija;izoliacija;degimas.;fire;risk;wiring;insulation;combustion
Abstract: Kas dešimto Lietuvoje kilusio gaisro priežastimi yra netvarkingos elektros įrangos ir instaliacijos eksploatavimas. Dėl ilgalaikio pastatų ir statinių elektros instaliacijos eksploatavimo prastėja jos dielektrinės savybės bei mechaninis ir šiluminis atsparumas per didelių elektros srovių ir viršįtampių poveikiui. Tokios izoliacinės laidų ir kabelių dangos dažniau užsidega, o ugnis plinta sparčiau ir gali tapti uždegimo šaltiniu. Tokių elektrosauginiu požiūriu pavojingų pastatų skaičius ypač didelis kaimo vietovėse, o skirtingos eksploatacijos trukmės elektros instaliacijos įtaka gaisrų rizikai yra didelė. Šiame darbe tirtos izoliacinių medžiagų laidų ir kabelių degumo savybės ugnies plitimo greičio požiūriu. Darbo tikslas: ištirti pastatų elektros instaliacijos ilgalaikio eksploatavimo įtaką gaisro rizikai. Atliktų eksperimentinių tyrimų rezultatai rodo, jog senos PVC, plastiko ir dažais dengto plastiko elektros instaliacijos degimo greitis yra mažiausias (iki 125 mm/min), o ilgai eksploatuotų laidų ir kabelių su gumos izoliacija degimo greitis gali būti iki 230 mm/min. Tyrimais nustatyta, jog ilgalaikio eksploatavimo nerenovuotos pastato elektros instaliacijos gaisro rizika yra 2 – 3 kartus didesnė.
Ten percent of overall number of fires at building is caused by electrical equipment and wiring faults in Lithuania. The long-term usage of wiring at buildings and structures deteriorate the dielectric properties, mechanical and thermal resistance of a large electrical currents and surge effects. Wire and cable coatings often ignite because of long-term exploitation and can cause rapid fire spread, which can become a source of ignition. Such circumstances are most common in rural areas where the amount of potentially dangerous objects is plenty. This study explores the firing features of coatings of various exploi-tation durations by implementing the method of flame spreading speed. The aim of the study was to assess the influence of long-term exploitation of electrical wiring in buildings on the fire risk. The data obtained experimentally show that the old cable coatings of PVC, plastic and painted plastic has the least speed of flame spreading (up to 125 mm/min). For the cables with rubber coating the flame spread speed was found to be as much as 230 mm/min. It was found that long-term exploitation of non-renovated building wiring increase the fire risk from 2 to 3 times.
Internet: https://hdl.handle.net/20.500.12259/112545
Appears in Collections:VDU, ASU ir LEU iki / until 2018

Files in This Item:
Show full item record
Export via OAI-PMH Interface in XML Formats
Export to Other Non-XML Formats


CORE Recommender

Page view(s)

8
checked on Jun 6, 2021

Download(s)

151
checked on Jun 6, 2021

Google ScholarTM

Check


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.